| General information | ||
| Product type designation | CPU 315-2 DP | |
| HW functional status | 01 | |
| Firmware version | V3.3 | |
| Product function | ||
| ¡ñ Isochronous mode | Yes | |
| Engineering with | ||
| ¡ñ Programming package | STEP 7 V5.5 + SP1 or higher or STEP 7 V5.2 + SP1 or higher with HSP 218 | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| external protection for power supply lines (recommendation) | 2 A min. | |
| Mains buffering | ||
| ¡ñ Mains/voltage failure stored energy time | 5 ms | |
| ¡ñ Repeat rate, min. | 1 s | |
| Input current | ||
| Current consumption (rated value) | 850 mA | |
| Current consumption (in no-load operation), typ. | 150 mA | |
| Inrush current, typ. | 3.5 A | |
| I²t | 1 A²·s | |
| Power loss | ||
| Power loss, typ. | 4.5 W | |
| Memory | ||
| Work memory | ||
| ¡ñ integrated | 256 kbyte | |
| ¡ñ expandable | No | |
| Load memory | ||
| ¡ñ Plug-in (MMC) | Yes | |
| ¡ñ Plug-in (MMC), max. | 8 Mbyte | |
| ¡ñ Data management on MMC (after last programming), min. | 10 a | |
| Backup | ||
| ¡ñ present | Yes; Guaranteed by MMC (maintenance-free) | |
| ¡ñ without battery | Yes; Program and data | |
| CPU processing times | ||
| for bit operations, typ. | 0.05 µs | |
| for word operations, typ. | 0.09 µs | |
| for fixed point arithmetic, typ. | 0.12 µs | |
| for floating point arithmetic, typ. | 0.45 µs | |
| CPU-blocks | ||
| Number of blocks (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. | |
| DB | ||
| ¡ñ Number, max. | 1 024; Number range: 1 to 16000 | |
| ¡ñ Size, max. | 64 kbyte | |
| FB | ||
| ¡ñ Number, max. | 1 024; Number range: 0 to 7999 | |
| ¡ñ Size, max. | 64 kbyte | |
| FC | ||
| ¡ñ Number, max. | 1 024; Number range: 0 to 7999 | |
| ¡ñ Size, max. | 64 kbyte | |
| OB | ||
| ¡ñ Number, max. | see instruction list | |
| ¡ñ Size, max. | 64 kbyte | |
| ¡ñ Number of free cycle OBs | 1; OB 1 | |
| ¡ñ Number of time alarm OBs | 1; OB 10 | |
| ¡ñ Number of delay alarm OBs | 2; OB 20, 21 | |
| ¡ñ Number of cyclic interrupt OBs | 4; OB 32, 33, 34, 35 | |
| ¡ñ Number of process alarm OBs | 1; OB 40 | |
| ¡ñ Number of DPV1 alarm OBs | 3; OB 55, 56, 57 | |
| ¡ñ Number of isochronous mode OBs | 1; OB 61 | |
| ¡ñ Number of startup OBs | 1; OB 100 | |
| ¡ñ Number of asynchronous error OBs | 5; OB 80, 82, 85, 86, 87 | |
| ¡ñ Number of synchronous error OBs | 2; OB 121, 122 | |
| Nesting depth | ||
| ¡ñ per priority class | 16 | |
| ¡ñ additional within an error OB | 4 | |
| Counters, timers and their retentivity | ||
| S7 counter | ||
| ¡ñ Number | 256 | |
| Retentivity | ||
| — adjustable | Yes | |
| — preset | Z 0 to Z 7 | |
| Counting range | ||
| — lower limit | 0 | |
| — upper limit | 999 | |
| IEC counter | ||
| ¡ñ present | Yes | |
| ¡ñ Type | SFB | |
| ¡ñ Number | Unlimited (limited only by RAM capacity) | |
| S7 times | ||
| ¡ñ Number | 256 | |
| Retentivity | ||
| — adjustable | Yes | |
| — preset | No retentivity | |
| Time range | ||
| — lower limit | 10 ms | |
| — upper limit | 9 990 s | |
| IEC timer | ||
| ¡ñ present | Yes | |
| ¡ñ Type | SFB | |
| ¡ñ Number | Unlimited (limited only by RAM capacity) | |
| Data areas and their retentivity | ||
| Retentive data area (incl. timers, counters, flags), max. | 128 kbyte | |
| Flag | ||
| ¡ñ Size, max. | 2 048 byte | |
| ¡ñ Retentivity available | Yes; MB 0 to MB 2 047 | |
| ¡ñ Retentivity preset | MB 0 to MB 15 | |
| ¡ñ Number of clock memories | 8; 1 memory byte | |
| Data blocks | ||
| ¡ñ Retentivity adjustable | Yes; via non-retain property on DB | |
| ¡ñ Retentivity preset | Yes | |
| Local data | ||
| ¡ñ per priority class, max. | 32 kbyte; Max. 2 KB per block | |
| Address area | ||
| I/O address area | ||
| ¡ñ Inputs | 2 048 byte | |
| ¡ñ Outputs | 2 048 byte | |
| of which distributed | ||
| — Inputs | 2 048 byte | |
| — Outputs | 2 048 byte | |
| Process image | ||
| ¡ñ Inputs | 2 048 byte | |
| ¡ñ Outputs | 2 048 byte | |
| ¡ñ Inputs, adjustable | 2 048 byte | |
| ¡ñ Outputs, adjustable | 2 048 byte | |
| ¡ñ Inputs, default | 128 byte | |
| ¡ñ Outputs, default | 128 byte | |
| Subprocess images | ||
| ¡ñ Number of subprocess images, max. | 1 | |
| Digital channels | ||
| ¡ñ Inputs | 16 384 | |
| — of which central | 1 024 | |
| ¡ñ Outputs | 16 384 | |
| — of which central | 1 024 | |
| Analog channels | ||
| ¡ñ Inputs | 1 024 | |
| — of which central | 256 | |
| ¡ñ Outputs | 1 024 | |
| — of which central | 256 | |
| Hardware configuration | ||
| Number of expansion units, max. | 3 | |
| Number of DP masters | ||
| ¡ñ integrated | 1 | |
| ¡ñ via CP | 4 | |
| Number of operable FMs and CPs (recommended) | ||
| ¡ñ FM | 8 | |
| ¡ñ CP, PtP | 8 | |
| ¡ñ CP, LAN | 10 | |
| Rack | ||
| ¡ñ Racks, max. | 4 | |
| ¡ñ Modules per rack, max. | 8 | |
| Time of day | ||
| Clock | ||
| ¡ñ Hardware clock (real-time) | Yes | |
| ¡ñ retentive and synchronizable | Yes | |
| ¡ñ Backup time | 6 wk; At 40 °C ambient temperature | |
| ¡ñ Deviation per day, max. | 10 s; Typ.: 2 s | |
| ¡ñ Behavior of the clock following POWER-ON | Clock continues running after POWER OFF | |
| ¡ñ Behavior of the clock following expiry of backup period | the clock continues at the time of day it had when power was switched off | |
| Operating hours counter | ||
| ¡ñ Number | 1 | |
| ¡ñ Number/Number range | 0 | |
| ¡ñ Range of values | 0 to 2^31 hours (when using SFC 101) | |
| ¡ñ Granularity | 1 h | |
| ¡ñ retentive | Yes; Must be restarted at each restart | |
| Clock synchronization | ||
| ¡ñ supported | Yes | |
| ¡ñ to MPI, master | Yes | |
| ¡ñ on MPI, device | Yes | |
| ¡ñ to DP, master | Yes; With DP slave only slave clock | |
| ¡ñ on DP, device | Yes | |
| ¡ñ in AS, master | Yes | |
| ¡ñ in AS, device | No | |
| Digital inputs | ||
| Number of digital inputs | 0 | |
| Digital outputs | ||
| Number of digital outputs | 0 | |
| Analog inputs | ||
| Number of analog inputs | 0 | |
| Interfaces | ||
| Number of PROFINET interfaces | 0 | |
| Number of RS 485 interfaces | 2; MPI and PROFIBUS DP | |
| Number of RS 422 interfaces | 0 | |
| 1. Interface | ||
| Interface type | Integrated RS 485 interface | |
| Isolated | No | |
| Interface types | ||
| ¡ñ RS 485 | Yes | |
| ¡ñ Output current of the interface, max. | 200 mA | |
| Protocols | ||
| ¡ñ MPI | Yes | |
| ¡ñ PROFIBUS DP master | No | |
| ¡ñ PROFIBUS DP device | No | |
| ¡ñ Point-to-point connection | No | |
| MPI | ||
| ¡ñ Transmission rate, max. | 187.5 kbit/s | |
| Services | ||
| — PG/OP communication | Yes | |
| — Routing | Yes | |
| — Global data communication | Yes | |
| — S7 basic communication | Yes | |
| — S7 communication | Yes; Only server, configured on one side | |
| — S7 communication, as client | No | |
| — S7 communication, as server | Yes | |
| 2. Interface | ||
| Interface type | Integrated RS 485 interface | |
| Isolated | Yes | |
| Interface types | ||
| ¡ñ RS 485 | Yes | |
| ¡ñ Output current of the interface, max. | 200 mA | |
| Protocols | ||
| ¡ñ MPI | No | |
| ¡ñ PROFIBUS DP master | Yes | |
| ¡ñ PROFIBUS DP device | Yes | |
| ¡ñ Point-to-point connection | No | |
| PROFIBUS DP master | ||
| ¡ñ Transmission rate, max. | 12 Mbit/s | |
| ¡ñ max. number of DP devices | 124; Per station | |
| Services | ||
| — PG/OP communication | Yes | |
| — Routing | Yes | |
| — Global data communication | No | |
| — S7 basic communication | Yes; I blocks only | |
| — S7 communication | Yes; Only server, configured on one side | |
| — S7 communication, as client | No | |
| — S7 communication, as server | Yes | |
| — Equidistance | Yes | |
| — Isochronous mode | Yes; OB 61 | |
| — SYNC/FREEZE | Yes | |
| — activation/deactivation of DP devices | Yes | |
| — max. number of DP devices that can be activated/deactivated at the same time | 8 | |
| — DPV1 | Yes | |
| Address area | ||
| — Inputs, max. | 2 048 byte | |
| — Outputs, max. | 2 048 byte | |
| User data per DP device | ||
| — Inputs, max. | 244 byte | |
| — Outputs, max. | 244 byte | |
| 2nd interface / PROFIBUS DP device / header | ||
| ¡ñ GSD file | The latest GSD file is available at: http://www.siemens.com/profibus-gsd | |
| ¡ñ Transmission rate, max. | 12 Mbit/s | |
| ¡ñ automatic baud rate search | Yes; only with passive interface | |
| ¡ñ Address area, max. | 32 | |
| ¡ñ User data per address area, max. | 32 byte | |
| Services | ||
| — PG/OP communication | Yes | |
| — Routing | Yes; Only with active interface | |
| — Global data communication | No | |
| — S7 basic communication | No | |
| — S7 communication | Yes; Only server, configured on one side | |
| — S7 communication, as client | No | |
| — S7 communication, as server | Yes | |
| — Direct data exchange (slave-to-slave communication) | Yes | |
| — DPV1 | No | |
| Transfer memory | ||
| — Inputs | 244 byte | |
| — Outputs | 244 byte | |
| Protocols | ||
| PROFIsafe | No | |
| communication functions / header | ||
| PG/OP communication | Yes | |
| Data record routing | Yes | |
| Global data communication | ||
| ¡ñ supported | Yes | |
| ¡ñ Number of GD loops, max. | 8 | |
| ¡ñ Number of GD packets, max. | 8 | |
| ¡ñ Number of GD packets, transmitter, max. | 8 | |
| ¡ñ Number of GD packets, receiver, max. | 8 | |
| ¡ñ Size of GD packets, max. | 22 byte | |
| ¡ñ Size of GD packet (of which consistent), max. | 22 byte | |
| S7 basic communication | ||
| ¡ñ supported | Yes | |
| ¡ñ User data per job, max. | 76 byte | |
| ¡ñ User data per job (of which consistent), max. | 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) | |
| S7 communication | ||
| ¡ñ supported | Yes | |
| ¡ñ as server | Yes | |
| ¡ñ as client | Yes; Via CP and loadable FB | |
| ¡ñ User data per job, max. | 180 byte; With PUT/GET | |
| ¡ñ User data per job (of which consistent), max. | 240 byte; as server | |
| S5 compatible communication | ||
| ¡ñ supported | Yes; via CP and loadable FC | |
| Number of connections | ||
| ¡ñ overall | 16 | |
| ¡ñ usable for PG communication | 15 | |
| — reserved for PG communication | 1 | |
| — adjustable for PG communication, min. | 1 | |
| — adjustable for PG communication, max. | 15 | |
| ¡ñ usable for OP communication | 15 | |
| — reserved for OP communication | 1 | |
| — adjustable for OP communication, min. | 1 | |
| — adjustable for OP communication, max. | 15 | |
| ¡ñ usable for S7 basic communication | 12 | |
| — reserved for S7 basic communication | 0 | |
| — adjustable for S7 basic communication, min. | 0 | |
| — adjustable for S7 basic communication, max. | 12 | |
| S7 message functions | ||
| Number of login stations for message functions, max. | 16; Depending on the configured connections for PG/OP and S7 basic communication | |
| Process diagnostic messages | Yes | |
| simultaneously active Alarm_S blocks, max. | 300 | |
| Test commissioning functions | ||
| Status block | Yes; Up to 2 simultaneously | |
| Single step | Yes | |
| Number of breakpoints | 4 | |
| Status/control | ||
| ¡ñ Status/control variable | Yes | |
| ¡ñ Variables | Inputs, outputs, memory bits, DB, times, counters | |
| ¡ñ Number of variables, max. | 30 | |
| — of which status variables, max. | 30 | |
| — of which control variables, max. | 14 | |
| Forcing | ||
| ¡ñ Forcing | Yes | |
| ¡ñ Forcing, variables | Inputs, outputs | |
| ¡ñ Number of variables, max. | 10 | |
| Diagnostic buffer | ||
| ¡ñ present | Yes | |
| ¡ñ Number of entries, max. | 500 | |
| — adjustable | No | |
| — of which powerfail-proof | 100; Only the last 100 entries are retained | |
| ¡ñ Number of entries readable in RUN, max. | ||
| — adjustable | Yes; From 10 to 499 | |
| — preset | 10 | |
| Service data | ||
| ¡ñ can be read out | Yes | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ¡ñ min. | 0 °C | |
| ¡ñ max. | 60 °C | |
| configuration / header | ||
| Configuration software | ||
| ¡ñ STEP 7 | Yes; V5.2 SP1 or higher with HW update | |
| configuration / programming / header | ||
| ¡ñ Command set | see instruction list | |
| ¡ñ Nesting levels | 8 | |
| ¡ñ System functions (SFC) | see instruction list | |
| ¡ñ System function blocks (SFB) | see instruction list | |
| Programming language | ||
| — LAD | Yes | |
| — FBD | Yes | |
| — STL | Yes | |
| — SCL | Yes | |
| — CFC | Yes | |
| — GRAPH | Yes | |
| — HiGraph® | Yes | |
| Know-how protection | ||
| ¡ñ User program protection/password protection | Yes | |
| ¡ñ Block encryption | Yes; With S7 block Privacy | |
| Dimensions | ||
| Width | 40 mm | |
| Height | 125 mm | |
| Depth | 130 mm | |
| Weights | ||
| Weight, approx. | 290 g | |





MY 4513
BR 4217
US 3084
CN 1549
SG 663
AR 426
GB 371
MX 319