input |
type of the power supply network |
1-phase AC |
supply voltage at AC |
Automatic range selection |
supply voltage |
120 V/230 V |
input voltage 1 at AC |
85 ... 132 V |
input voltage 2 at AC |
170 ... 264 V |
wide range input |
No |
buffering time for rated value of the output current in the event of power failure minimum |
35 ms |
operating condition of the mains buffering |
at Vin = 120/230 V |
line frequency |
50/60 Hz |
line frequency |
47 ... 63 Hz |
input current |
|
¡ñ at rated input voltage 120 V |
2.1 A |
¡ñ at rated input voltage 230 V |
1.2 A |
current limitation of inrush current at 25 °C maximum |
10 A |
I2t value maximum |
0.2 A²·s |
fuse protection type |
T 3.15 A (not accessible) |
fuse protection type in the feeder |
Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V |
output |
voltage curve at output |
Controlled, isolated DC voltage |
output voltage at DC rated value |
24 V |
output voltage |
|
¡ñ at output 1 at DC rated value |
24 V |
|
|
output voltage adjustable |
Yes; via potentiometer |
adjustable output voltage |
24 ... 28.8 V; max. 120 W |
relative overall tolerance of the voltage |
3 % |
relative control precision of the output voltage |
|
¡ñ on slow fluctuation of input voltage |
0.1 % |
¡ñ on slow fluctuation of ohm loading |
0.2 % |
residual ripple |
|
¡ñ maximum |
50 mV |
voltage peak |
|
¡ñ maximum |
200 mV |
display version for normal operation |
Green LED for 24 V OK |
type of signal at output |
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" |
behavior of the output voltage when switching on |
Overshoot of Vout approx. 3 % |
response delay maximum |
1.5 s |
voltage increase time of the output voltage |
|
¡ñ typical |
30 ms |
output current |
|
¡ñ rated value |
5 A |
¡ñ rated range |
0 ... 5 A; As of Ua>24 V: 4% [Ia]/V [Ua]; at Ue<100 V/<200 V: 80% Ia rated |
|
|
supplied active power typical |
120 W |
short-term overload current |
|
¡ñ at short-circuit during operation typical |
15 A |
duration of overloading capability for excess current |
|
¡ñ at short-circuit during operation |
25 ms |
constant overload current |
|
¡ñ on short-circuiting during the start-up typical |
6 A |
bridging of equipment |
Yes; switchable characteristic |
number of parallel-switched equipment resources for increasing the power |
2 |
efficiency |
efficiency in percent |
93 % |
power loss [W] |
|
¡ñ at rated output voltage for rated value of the output current typical |
9 W |
¡ñ during no-load operation maximum |
1.5 W |
closed-loop control |
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.1 % |
relative control precision of the output voltage load step of resistive load 50/100/50 % typical |
2 % |
setting time |
|
¡ñ load step 50 to 100% typical |
0.25 ms |
¡ñ load step 100 to 50% typical |
0.5 ms |
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
2 % |
setting time |
|
¡ñ load step 10 to 90% typical |
0.25 ms |
¡ñ load step 90 to 10% typical |
0.5 ms |
¡ñ maximum |
1 ms |
protection and monitoring |
design of the overvoltage protection |
< 33 V |
property of the output short-circuit proof |
Yes |
design of short-circuit protection |
Alternatively, constant current characteristic approx. 6 A or latching shutdown |
¡ñ typical |
6 A |
overcurrent overload capability |
|
¡ñ in normal operation |
overload capability 150 % Iout rated up to 5 s/min |
enduring short circuit current RMS value |
|
¡ñ typical |
6 A |
display version for overload and short circuit |
LED yellow for "overload", LED red for "latching shutdown" |
safety |
galvanic isolation between input and output |
Yes |
galvanic isolation |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
operating resource protection class |
Class I |
leakage current |
|
¡ñ maximum |
3.5 mA |
¡ñ typical |
1 mA |
protection class IP |
IP20 |
EMC |
standard |
|
¡ñ for emitted interference |
EN 55022 Class B |
¡ñ for mains harmonics limitation |
EN 61000-3-2 |
¡ñ for interference immunity |
EN 61000-6-2 |
standards, specifications, approvals |
certificate of suitability |
|
¡ñ CE marking |
Yes |
¡ñ UL approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) |
¡ñ CSA approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) |
¡ñ EAC approval |
Yes |
¡ñ Regulatory Compliance Mark (RCM) |
Yes |
¡ñ NEC Class 2 |
No |
type of certification |
|
¡ñ BIS |
Yes; R-41183539 |
¡ñ CB-certificate |
Yes |
MTBF at 40 °C |
1 421 519 h |
standards, specifications, approvals hazardous environments |
certificate of suitability |
|
¡ñ IECEx |
No |
¡ñ ATEX |
No |
¡ñ ULhazloc approval |
No |
¡ñ cCSAus, Class 1, Division 2 |
No |
¡ñ FM registration |
No |
standards, specifications, approvals marine classification |
shipbuilding approval |
Yes |
Marine classification association |
|
¡ñ American Bureau of Shipping Europe Ltd. (ABS) |
Yes |
¡ñ French marine classification society (BV) |
No |
¡ñ Det Norske Veritas (DNV) |
Yes |
¡ñ Lloyds Register of Shipping (LRS) |
No |
standards, specifications, approvals Environmental Product Declaration |
Environmental Product Declaration |
Yes |
global warming potential [CO2 eq] |
|
¡ñ total |
294.6 kg |
¡ñ during manufacturing |
12.6 kg |
¡ñ during operation |
281.6 kg |
¡ñ after end of life |
0.18 kg |
ambient conditions |
ambient temperature |
|
¡ñ during operation |
-25 ... +70 °C; With natural convection; startup tested starting from -40 °C nominal voltage |
¡ñ during transport |
-40 ... +85 °C |
¡ñ during storage |
-40 ... +85 °C |
environmental category according to IEC 60721 |
Climate class 3K3, 5 ... 95% no condensation |
connection method |
type of electrical connection |
screw terminal |
¡ñ at input |
L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm² single-core/finely stranded |
¡ñ at output |
+, -: 2 screw terminals each for 0.2 ... 2.5 mm² |
¡ñ for auxiliary contacts |
13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²; 15, 16 (Remote): 1 screw terminal each for 0.14 ... 1.5 mm² |
mechanical data |
width × height × depth of the enclosure |
45 × 125 × 125 mm |
installation width × mounting height |
45 mm × 225 mm |
required spacing |
|
¡ñ top |
50 mm |
¡ñ bottom |
50 mm |
¡ñ left |
0 mm |
¡ñ right |
0 mm |
fastening method |
Snaps onto DIN rail EN 60715 35x7.5/15 |
¡ñ DIN-rail mounting |
Yes |
¡ñ S7 rail mounting |
No |
¡ñ wall mounting |
No |
housing can be lined up |
Yes |
net weight |
0.8 kg |