General technical data |
product brand name |
|
SIRIUS |
product designation |
|
Soft starter |
product feature |
|
|
¡ñ integrated bypass contact system |
|
Yes |
¡ñ thyristors |
|
Yes |
product function |
|
|
¡ñ intrinsic device protection |
|
Yes |
¡ñ motor overload protection |
|
Yes |
¡ñ evaluation of thermistor motor protection |
|
No |
¡ñ external reset |
|
Yes |
¡ñ adjustable current limitation |
|
Yes |
¡ñ inside-delta circuit |
|
No |
product component motor brake output |
|
No |
insulation voltage rated value |
V |
600 |
degree of pollution |
|
3, acc. to IEC 60947-4-2 |
blocking voltage of the thyristor maximum |
V |
1 600 |
reference code according to EN 61346-2 |
|
Q |
reference code according to DIN 40719 extended according to IEC 204-2 according to IEC 750 |
|
G |
Power Electronics |
operational current |
|
|
¡ñ at 40 °C rated value |
A |
32 |
¡ñ at 50 °C rated value |
A |
29 |
¡ñ at 60 °C rated value |
A |
26 |
yielded mechanical performance for 3-phase motors |
|
|
¡ñ at 230 V |
|
|
— at standard circuit at 40 °C rated value |
kW |
7.5 |
¡ñ at 400 V |
|
|
— at standard circuit at 40 °C rated value |
kW |
15 |
yielded mechanical performance [hp] for 3-phase AC motor at 200/208 V at standard circuit at 50 °C rated value |
hp |
7.5 |
operating frequency rated value |
Hz |
50 ... 60 |
relative negative tolerance of the operating frequency |
% |
-10 |
relative positive tolerance of the operating frequency |
% |
10 |
operating voltage at standard circuit rated value |
V |
200 ... 480 |
relative negative tolerance of the operating voltage at standard circuit |
% |
-15 |
relative positive tolerance of the operating voltage at standard circuit |
% |
10 |
minimum load [%] |
% |
20 |
adjustable motor current for motor overload protection minimum rated value |
A |
17 |
continuous operating current [% of Ie] at 40 °C |
% |
115 |
power loss [W] at operational current at 40 °C during operation typical |
W |
13 |
Control circuit/ Control |
type of voltage of the control supply voltage |
|
AC/DC |
control supply voltage frequency 1 rated value |
Hz |
50 |
control supply voltage frequency 2 rated value |
Hz |
60 |
relative negative tolerance of the control supply voltage frequency |
% |
-10 |
relative positive tolerance of the control supply voltage frequency |
% |
10 |
control supply voltage 1 at AC at 50 Hz |
V |
110 ... 230 |
control supply voltage 1 at AC at 60 Hz |
V |
110 ... 230 |
relative negative tolerance of the control supply voltage at AC at 50 Hz |
% |
-15 |
relative positive tolerance of the control supply voltage at AC at 50 Hz |
% |
10 |
relative negative tolerance of the control supply voltage at AC at 60 Hz |
% |
-15 |
relative positive tolerance of the control supply voltage at AC at 60 Hz |
% |
10 |
control supply voltage 1 at DC |
V |
110 ... 230 |
relative negative tolerance of the control supply voltage at DC |
% |
-15 |
relative positive tolerance of the control supply voltage at DC |
% |
10 |
display version for fault signal |
|
red |
Mechanical data |
size of engine control device |
|
S0 |
width |
mm |
45 |
height |
mm |
125 |
depth |
mm |
155 |
fastening method |
|
screw and snap-on mounting |
mounting position |
|
With additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t |
required spacing with side-by-side mounting |
|
|
¡ñ upwards |
mm |
60 |
¡ñ at the side |
mm |
15 |
¡ñ downwards |
mm |
40 |
wire length maximum |
m |
300 |
number of poles for main current circuit |
|
3 |
Connections/ Terminals |
type of electrical connection |
|
|
¡ñ for main current circuit |
|
screw-type terminals |
¡ñ for auxiliary and control circuit |
|
screw-type terminals |
number of NC contacts for auxiliary contacts |
|
0 |
number of NO contacts for auxiliary contacts |
|
2 |
number of CO contacts for auxiliary contacts |
|
1 |
type of connectable conductor cross-sections for main contacts for box terminal using the front clamping point |
|
|
¡ñ solid |
|
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), max. 1x 10 mm² |
¡ñ finely stranded with core end processing |
|
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²) |
type of connectable conductor cross-sections for AWG cables for main contacts for box terminal |
|
|
¡ñ using the front clamping point |
|
1x 8, 2x (16 ... 10) |
type of connectable conductor cross-sections for auxiliary contacts |
|
|
¡ñ solid |
|
2x (0.5 ... 2.5 mm²) |
¡ñ finely stranded with core end processing |
|
2x (0.5 ... 1.5 mm²) |
type of connectable conductor cross-sections for AWG cables |
|
|
¡ñ for auxiliary contacts |
|
2x (20 ... 14) |
¡ñ for auxiliary contacts finely stranded with core end processing |
|
2x (20 ... 16) |
Ambient conditions |
installation altitude at height above sea level |
m |
5 000 |
environmental category |
|
|
¡ñ during transport according to IEC 60721 |
|
2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m) |
¡ñ during storage according to IEC 60721 |
|
1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4 |
¡ñ during operation according to IEC 60721 |
|
3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
ambient temperature |
|
|
¡ñ during operation |
°C |
-25 ... +60 |
¡ñ during storage |
°C |
-40 ... +80 |
derating temperature |
°C |
40 |
protection class IP on the front according to IEC 60529 |
|
IP20 |
touch protection on the front according to IEC 60529 |
|
finger-safe, for vertical contact from the front |
Environmental footprint |
Environmental Product Declaration(EPD) |
|
Yes |
global warming potential [CO2 eq] total |
kg |
121 |
global warming potential [CO2 eq] during manufacturing |
kg |
4.24 |
global warming potential [CO2 eq] during sales |
kg |
0.207 |
global warming potential [CO2 eq] during operation |
kg |
117 |
global warming potential [CO2 eq] after end of life |
kg |
-0.229 |
UL/CSA ratings |
yielded mechanical performance [hp] for 3-phase AC motor |
|
|
¡ñ at 220/230 V |
|
|
— at standard circuit at 50 °C rated value |
hp |
7.5 |
¡ñ at 460/480 V |
|
|
— at standard circuit at 50 °C rated value |
hp |
20 |
contact rating of auxiliary contacts according to UL |
|
B300 / R300 |