| input | ||
| type of the power supply network | 1-phase AC or DC | |
| supply voltage at AC | ||
| ¡ñ minimum rated value | 100 V | |
| ¡ñ maximum rated value | 240 V | |
| ¡ñ initial value | 85 V | |
| ¡ñ full-scale value | 264 V | |
| input voltage at DC | 110 ... 300 V | |
| wide range input | Yes | |
| overvoltage overload capability | 300 V AC for 1 s | |
| buffering time for rated value of the output current in the event of power failure minimum | 40 ms | |
| operating condition of the mains buffering | at Vin = 187 V | |
| line frequency | 50/60 Hz | |
| line frequency | 47 ... 63 Hz | |
| input current | ||
| ¡ñ at rated input voltage 120 V | 0.3 A | |
| ¡ñ at rated input voltage 230 V | 0.2 A | |
| current limitation of inrush current at 25 °C maximum | 20 A | |
| I2t value maximum | 0.8 A²·s | |
| fuse protection type | internal | |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic C | |
| output | ||
| voltage curve at output | Controlled, isolated DC voltage | |
| output voltage at DC rated value | 24 V | |
| output voltage | ||
| ¡ñ at output 1 at DC rated value | 24 V | |
| output voltage adjustable | No | |
| relative overall tolerance of the voltage | 3 % | |
| relative control precision of the output voltage | ||
| ¡ñ on slow fluctuation of input voltage | 0.1 % | |
| ¡ñ on slow fluctuation of ohm loading | 0.1 % | |
| residual ripple | ||
| ¡ñ maximum | 200 mV | |
| ¡ñ typical | 30 mV | |
| voltage peak | ||
| ¡ñ maximum | 300 mV | |
| ¡ñ typical | 50 mV | |
| display version for normal operation | Green LED for output voltage OK | |
| behavior of the output voltage when switching on | No overshoot of Vout (soft start) | |
| response delay maximum | 0.5 s | |
| voltage increase time of the output voltage | ||
| ¡ñ typical | 100 ms | |
| output current | ||
| ¡ñ rated value | 0.6 A | |
| ¡ñ rated range | 0 ... 0.6 A; +55 ... +70 °C: Derating 2%/K | |
| supplied active power typical | 14.4 W | |
| bridging of equipment | No | |
| efficiency | ||
| efficiency in percent | 81 % | |
| power loss [W] | ||
| ¡ñ at rated output voltage for rated value of the output current typical | 3.4 W | |
| ¡ñ during no-load operation maximum | 0.3 W | |
| closed-loop control | ||
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.2 % | |
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 2 % | |
| setting time | ||
| ¡ñ load step 10 to 90% typical | 1 ms | |
| ¡ñ load step 90 to 10% typical | 1 ms | |
| protection and monitoring | ||
| design of the overvoltage protection | Yes, according to EN 60950-1 | |
| property of the output short-circuit proof | Yes | |
| design of short-circuit protection | Constant current characteristic | |
| ¡ñ typical | 0.8 A | |
| overcurrent overload capability | ||
| ¡ñ when switching on | 150% Iout rated typ. 200 ms | |
| ¡ñ in normal operation | overload capability 150% Iout rated typ. 200 ms | |
| enduring short circuit current RMS value | ||
| ¡ñ maximum | 0.8 A | |
| measuring point for output current | No | |
| safety | ||
| galvanic isolation between input and output | Yes | |
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | |
| operating resource protection class | Class II (without protective conductor) | |
| protection class IP | IP20 | |
| EMC | ||
| standard | ||
| ¡ñ for emitted interference | EN 55022 Class B | |
| ¡ñ for mains harmonics limitation | not applicable | |
| ¡ñ for interference immunity | EN 61000-6-2 | |
| standards, specifications, approvals | ||
| certificate of suitability | ||
| ¡ñ CE marking | Yes | |
| ¡ñ UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) | |
| ¡ñ CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) | |
| ¡ñ EAC approval | Yes | |
| ¡ñ NEC Class 2 | Yes; according to UL1310, File E151273 | |
| ¡ñ SEMI F47 | Yes | |
| type of certification | ||
| ¡ñ CB-certificate | Yes | |
| MTBF at 40 °C | 4 415 040 h | |
| standards, specifications, approvals hazardous environments | ||
| certificate of suitability | ||
| ¡ñ IECEx | No | |
| ¡ñ ATEX | No | |
| ¡ñ ULhazloc approval | No | |
| ¡ñ cCSAus, Class 1, Division 2 | No | |
| ¡ñ FM registration | No | |
| standards, specifications, approvals marine classification | ||
| shipbuilding approval | Yes | |
| Marine classification association | ||
| ¡ñ American Bureau of Shipping Europe Ltd. (ABS) | Yes | |
| ¡ñ French marine classification society (BV) | Yes | |
| ¡ñ Det Norske Veritas (DNV) | Yes | |
| ¡ñ Lloyds Register of Shipping (LRS) | Yes | |
| standards, specifications, approvals Environmental Product Declaration | ||
| Environmental Product Declaration | Yes | |
| global warming potential [CO2 eq] | ||
| ¡ñ total | 94.5 kg | |
| ¡ñ during manufacturing | 1.3 kg | |
| ¡ñ during operation | 93.1 kg | |
| ¡ñ after end of life | 0.05 kg | |
| ambient conditions | ||
| ambient temperature | ||
| ¡ñ during operation | -25 ... +70 °C; with natural convection | |
| ¡ñ during transport | -40 ... +85 °C | |
| ¡ñ during storage | -40 ... +85 °C | |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation | |
| connection method | ||
| type of electrical connection | screw terminal | |
| ¡ñ at input | L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded | |
| ¡ñ at output | +, -: 1 screw terminal each for 0.5 ... 2.5 mm² | |
| ¡ñ for auxiliary contacts | - | |
| mechanical data | ||
| width × height × depth of the enclosure | 18 × 90 × 53 mm | |
| installation width × mounting height | 18 mm × 130 mm | |
| required spacing | ||
| ¡ñ top | 20 mm | |
| ¡ñ bottom | 20 mm | |
| ¡ñ left | 0 mm | |
| ¡ñ right | 0 mm | |
| fastening method | Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions | |
| ¡ñ DIN-rail mounting | Yes | |
| ¡ñ S7 rail mounting | No | |
| ¡ñ wall mounting | Yes | |
| housing can be lined up | Yes | |
| net weight | 0.07 kg | |





BR 22569
VN 8663
MY 5250
US 3427
AR 2093
CN 1836
EC 1007
IN 951