| Maxtron MX-2000EPR Series Rack Tower Convertible | 
			  | 
		
		
			| MODEL | 
			MX 2000EPR | 
		
		
			| Capacity | 
			2 kVA / 1800 W | 
		
		
			| INPUT | 
			  | 
		
		
			| Rated voltage | 
			208 / 220 / 230 / 240 Vac | 
		
		
			| Voltage range | 
			110 ~ 176 Vac (linear derating between 50% and 100% load);176 ~ 280 Vac (no derating);280 ~ 300 Vac (derating 50%) | 
		
		
			| Frequency | 
			40 ~ 70 Hz (auto-sensing) | 
		
		
			| Power factor | 
			≥0.99 | 
		
		
			| Bypass voltage range | 
			-25% ~ +15% (settable) | 
		
		
			| Total harmonic distortion (THDi) | 
			≤ 6% | 
		
		
			| OUTPUT | 
			  | 
		
		
			| Voltage | 
			208 / 220 / 230 / 240 Vac (settable via LCD) | 
		
		
			| Voltage regulation | 
			± 1% | 
		
		
			| Frequency | 
			45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range);50 / 60 Hz ± 0.1 Hz (battery mode) | 
		
		
			| Waveform | 
			Sinusoidal | 
		
		
			| Power factor | 
			0.9 | 
		
		
			| Total harmonic distortion (THDv) | 
			≤ 2% (linear load); ≤ 5% (non-linear load) | 
		
		
			| Crest factor | 
			3:01 | 
		
		
			| Overload | 
			105% ~ 125% for 1 min, 125% ~ 150% for 30s, > 150% for 300ms | 
		
		
			| BATTERIES | 
			  | 
		
		
			| DC voltage | 
			48 / 72 V (H) | 
		
		
			| Inbuilt battery | 
			/ | 
		
		
			| Charging curren (max.) | 
			6:00 AM | 
		
		
			| Recharger time | 
			Standard model : 90% capacity restored in 3 hours; Long time model : depend on the capacity of battery | 
		
		
			| SYSTEM | 
			  | 
		
		
			| Efficiency | 
			≥ 91% (Mains mode), ≥ 86% (Battery mode), ≥ 96% (ECO mode) | 
		
		
			| Transfer time | 
			Mains mode to battery mode : 0 ms Inverter mode to bypass mode; 4 ms (tupical) | 
		
		
			| Protections | 
			Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection | 
		
		
			| Communications | 
			RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) | 
		
		
			| Display | 
			LCD + LED | 
		
		
			| Standards | 
			EN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5,IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2,IEC 62040-2, IEC 6204001 | 
		
		
			| OTHER | 
			  | 
		
		
			| Operating temperature | 
			0¡æ ~ 40¡æ | 
		
		
			| Storage temperature | 
			-25¡æ ~ 55¡æ (without batteries) | 
		
		
			| Relative humidity | 
			0~95% (non-condensing) | 
		
		
			| Altitude | 
			≤ 1000 m, derating 1 % for each additional 100 m | 
		
		
			| IP rating | 
			IP 20 | 
		
		
			| Noise level at 1m | 
			≤ 50 dB | 
		
		
			| Dimensions ( W x D x H ) (mm) | 
			440 x 468 x 88 | 
		
		
			| Packaged dimensions ( W x D x H ) (mm) | 
			545 x 592 x 201 | 
		
		
			| Net weight (kg) | 
			9.7 | 
		
		
			| Gross weight (kg) | 
			13.2 |