DC-UPS IN: 120–230 Vac / OUT: 24 Vdc 5 A
Power supply with integrated battery charger
Suitable for Lead-Acid batteries
Supplies power to load and battery simultaneously
Battery protection (oveload and deep discharge)
LED status indicator and alarm contact
Code | XCSC120C |
---|---|
Type | CSC120C |
HS code | 85044083 |
INPUT TECHNICAL DATA | |
Input rated voltage | 120–230 Vac |
Input voltage AC | 90…264 Vac |
Input voltage DC | 100…345 Vdc (derating Uin |
Frequency | 47…63 Hz |
Current consumption | 1.9 A (120 Vac) / 1.1 A (230 Vac) |
Inrush peak current | 20 A |
Power factor | > 0.65 |
Internal protection fuse | T 3.15 A |
External protection on AC line | MCB: C-4 A / Fuse: T 4 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 24 Vdc |
Output adjustable range | 26…26 Vdc normal operation, 17…25 Vdc battery operation |
Continuous current | 5 A at 50°C |
Status indication | LED ''DC OK'' / LED ''Alarm'' |
Alarm contact | 1 dry contact (DC OK) |
Battery type | Lead-Acid |
Battery capacity | max. 1.2 Ah (24 Vdc) |
Charging current | 150 mA |
Battery disconnection voltage | ≤ 18 Vdc ±0.5 V |
Protection | reverse polarity, short-circuit, battery overload, battery deep discharge |
GENERAL TECHNICAL DATA | |
Efficiency | 84% (120 Vac) 86% (230 Vac) |
Dissipated power | 22 W (120 Vac) 19 W (230 Vac) |
Operating temperature range | –20…+60°C (derating -3.2 W >45°C) |
Input / output isolation | 3 KVac / 60 s (SELV output) |
Input / ground isolation | 1.5 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |
Standard / approvals | EN 60950-1 |
EMC Standard | EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 |
Overvoltage category / pollution degree | II / 2 |
Protection degree | IP 20 |
Connection terminal | 2.5 mm² / 2.5 mm² |
Housing material | aluminium |
Dimensions (LxHxD) | 40x130x115 mm |
Approximate weight | 450 g |
Mounting information | vertical on a rail, 10 mm from adjacent components |
ACCESSORIES | |
Mounting rail (IEC60715/TH35-7.5) | PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB |
Mounting rail (IEC60715/TH35-15) | PR/3/PP, PR/3/PP/ZB, PR/3/PA, PR/3/PA/ZB |
APPROVALS AND MARKINGS |
NOTES
Please refer to the datasheet or operating instruction for more details
In order to complete the charge, the DC output of the power supply must be 2-3V more than nominal voltage of the battery
For further information see PDF catalog