Model :
- 1769-OF2
Labelled Diagram :
.png)
Specifications :
| Specification | Value |
| Dimensions | 118 mm (height) x 87 mm (depth) x 35 mm (width) height including mounting tabs is 138 mm 4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in. |
| Approximate Shipping Weight (with carton) | 300g (0.65 lbs.) |
| Storage Temperature | -40°C to +85°C (-40°F to +185°F) |
| Operating Temperature | 0°C to +60°C (32°F to +140°F) |
| Operating Humidity | 5% to 95% non-condensing |
| Operating Altitude | 2000 meters (6561 feet) |
| Vibration | Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak Relay Operation: 2G |
| Shock | Operating: 30G, 11 ms panel mounted (20G, 11 ms DIN rail mounted) |
| Relay Operation: 7.5G panel mounted (5G DIN rail mounted) | |
| Non-Operating: 40G panel mounted (30G DIN rail mounted) | |
| Agency Certification | C-UL certified (under CSA C22.2 No. 142) |
| UL 508 listed | |
| CE compliant for all applicable directives | |
| Hazardous Environment Class | Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213) |
| Radiated and Conducted Emissions | EN50081-2 Class A |
| Electrical/EMC: | The module has passed testing at the following levels: |
| ESD Immunity (IEC1000-4-2) | 4 kV contact, 8 kV air, 4 kV indirect |
| Radiated Immunity (IEC1000-4-3) | 10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier |
| Fast Transient Burst (IEC1000-4-4) | 2 kV, 5 kHz |
| Surge Immunity (IEC1000-4-5) | 1 kV galvanic gun |
| Conducted Immunity (IEC1000-4-6) | 10V dc, 0.15 to 80 MHz(1) |