GT-4564
Analog output
-4 analog outputs
-10~10V
-16bit resolution
-10pt removable terminal block

General description
Article number |
100-8171 |
Warranty |
2 year |
Shock operating |
IEC 60068-2-27 (15G) |
Vibration resistence |
Sine vibration (based on IEC 60068-2-6), 5 ~ 25Hz: ±1.6mm, 25 ~ 300Hz: 4G, Sweep rate: 1 octave/min., 20 cycles, Random vibration (based on IEC 60068-2-64), 10 ~ 40Hz: 0.0125g²/Hz, 40 ~ 100Hz: 0.0125 → 0.002g²/Hz, 100 ~ 500Hz: 0.002 g²/Hz, 500 ~ 2000Hz: 0.002 → 1.3 x 10-4g²/Hz, Test time: 1hrs for each test |
Industrial emissions |
EN 61000-6-4/A11: 2011 |
Industrial immunity |
EN 61000-6-2: 2005 |
Installation position |
Horisontal, Vertical |
Product certifications |
CE, UL, FCC, RoHS, China RoHS, Reach |
Power dissipation |
Max. 30mA @ 5VDC, Max. 30mA @ 24VDC |
Isolation |
I/O to Logic: Photocoupler isolation, I/O to Field Power: Non-Isolation |
Field power |
Nominal supply voltage: 24VDC, Voltage range: 60℃: 18~32VDC, 70℃: 18~26.4VDC |
Weight |
60g |
Module size |
12x99x70mm |
Environmental
Mounting |
35mm DIN rail |
Operating temperature |
-40 ~ 70℃, Degraded performance > 60℃ |
Storage temperature |
-40 ~ 85℃ |
UL temperature |
-20 ~ 60℃ |
Relative humidity |
5 ~ 90% non-condensing |
Calibration |
Not Required |
Common type |
4 Common, Field Power 0V is Common(AGND) |
Conversion time |
≤0.2ms, all channels |
Data format |
16bit Integer (2' compliment) |
Diagnostics |
Field Power OFF: LED BLINK, Field Power ON: LED OFF (no output), Field Power ON: LED ON (output) |
Indicators |
4 green output status LEDs |
Load resistance |
Min. 4kΩ |
Module error |
±0.1% full scale @ 25℃, ±0.3% full scale @ -40°C, 70℃ |
Output format |
-10 ~ 10V |
Outputs per module |
4 channel single end |
Resolution in ranges |
0.31mV/bit |
more infomaion : https://www.crevis.ru/files/docs/[Spec]%20GT-4564%20(Rev%201.00).pdf