| General information | ||
| Product type designation | IM 153-1 DP ST | |
| Vendor identification (VendorID) | 801Dh | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 20.4 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| external protection for power supply lines (recommendation) | not necessary | |
| Mains buffering | ||
| ¡ñ Mains/voltage failure stored energy time | 5 ms | |
| Input current | ||
| Current consumption, max. | 350 mA; At 24 V DC | |
| Inrush current, typ. | 2.5 A | |
| I²t | 0.1 A²·s | |
| output voltage / header | ||
| Rated value (DC) | 5 V | |
| Output current | ||
| for backplane bus (5 V DC), max. | 1 A | |
| Power loss | ||
| Power loss, typ. | 3 W | |
| Address area | ||
| Addressing volume | ||
| ¡ñ Inputs | 128 byte | |
| ¡ñ Outputs | 128 byte | |
| Hardware configuration | ||
| number of modules per DP device interface, max. | 8 | |
| Interfaces | ||
| Transmission procedure | RS 485 | |
| Transmission rate, max. | 12 Mbit/s | |
| 1. Interface | ||
| automatic detection of transmission rate | Yes | |
| Interface types | ||
| ¡ñ Output current of the interface, max. | 90 mA | |
| ¡ñ Design of the connection | 9-pin sub D socket | |
| 1st interface / PROFIBUS DP device / header | ||
| ¡ñ GSD file | (for DPV1) SIEM801D.GSD; SI01801D.GSG | |
| ¡ñ automatic baud rate search | Yes | |
| Protocols | ||
| Bus protocol/transmission protocol | PROFIBUS DP to EN 50170 | |
| Protocols (Ethernet) | ||
| ¡ñ TCP/IP | No | |
| PROFIBUS DP | ||
| ¡ñ Number of node addresses, max. | 1 to 125 permitted | |
| Services | ||
| — SYNC capability | Yes | |
| — FREEZE capability | Yes | |
| — Direct data exchange (slave-to-slave communication) | Yes; Sender | |
| Potential separation | ||
| Potential separation exists | Yes | |
| Isolation | ||
| Isolation tested with | Isolation voltage 500 V | |
| Degree and class of protection | ||
| IP degree of protection | IP20 | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ¡ñ min. | 0 °C | |
| ¡ñ max. | 60 °C | |
| ¡ñ horizontal installation, min. | 0 °C | |
| ¡ñ horizontal installation, max. | 60 °C | |
| ¡ñ vertical installation, min. | 0 °C | |
| ¡ñ vertical installation, max. | 40 °C | |
| Altitude during operation relating to sea level | ||
| ¡ñ Installation altitude above sea level, max. | 3 000 m | |
| configuration / header | ||
| Configuration software | ||
| ¡ñ STEP 7 | STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file | |
| Dimensions | ||
| Width | 40 mm | |
| Height | 125 mm | |
| Depth | 117 mm | |
| Weights | ||
| Weight, approx. | 360 g | |









 
            
             
             
		



 BR                                22522
BR                                22522                             VN                                11423
VN                                11423                             US                                2699
US                                2699                             AR                                2189
AR                                2189                             CN                                1712
CN                                1712                             EC                                1028
EC                                1028                             MY                                1027
MY                                1027                             SG                                835
SG                                835                             
         
        