Model :
- CPM2A-60CDR-D
Features :
- Interrupt Inputs – Triggered when inputs 00003–00006 change OFF → ON; use subroutines 000–003.
- Interval Timer Interrupt – Executes interrupts with 0.1 ms precision; subroutines 000–049 can be assigned.
- Count-up Interrupt – Inputs 00003–00006 count pulses up to 2 kHz; interrupt occurs when count reaches SV.
- Count-check Interrupt – High-speed inputs 00000–00002 count up to 20 kHz or 5 kHz; interrupt occurs when PV = target value or within range.
- Interval Timer (CPM2) – One timer, 0.5 ms – 319,968 ms range, 0.1 ms precision, supports single or scheduled interrupts.
- High-speed Counter – Built-in counter up to 20 kHz; supports target or range comparison independent of PLC cycle time.
- Pulse Outputs – Two outputs supporting single-phase pulses, variable duty pulses, or trapezoidal acceleration/deceleration.
- PV Coordinate System – Can be set to relative or absolute in PLC setup.
- Synchronized Pulse Control – Combines high-speed counter + pulse output to generate pulses 10 Hz – 10 kHz proportional to input frequency.
Dimension :

Specifications :
| Item | CPU Units with 20 I/O points |
CPU Units with 30 I/O points |
CPU Units with 40 I/O points |
CPU Units with 60 I/O points |
|
| Supply voltage | AC power | 100 to 240 V AC, 50/60 Hz | |||
| DC power | 24 VDC | ||||
| Operating voltage range | AC power | 85 to 264 V AC | |||
| DC power | 20.4 to 26.4 V DC | ||||
| Power consumption | AC power | 60 VA max. | |||
| DC power | 20 W max. | ||||
| Inrush current | AC power | 60 A max. | |||
| DC power | 20 A max. | ||||
| External power supply (AC power supplies only) |
Supply voltage | 24 VDC | |||
| Output capacity | 300 mA | ||||
| Insulation resistance | 20 ΜΩ min. (at 500 V DC) between the external AC terminals and protective earth terminals | ||||
| Dielectric strength | 2,300 V AC 50/60 Hz for 1 min between the external AC and protective earth terminals, leakage current: 10 mA max. | ||||
| Noise immunity | Conforms to IEC61000-4-4, 2 kV (power lines) | ||||
| Vibration resistance | 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s² in X, Y, and Z directions for 80 minutes each (Time coefficient; 8 minutes x coefficient factor 10 = total time 80 minutes) |
||||
| Shock resistance | 147 m/s² three times each in X, Y, and Z directions | ||||
| Ambient temperature | Operating: 0° to 55°C | ||||
| Storage: -20° to 75° C | |||||
| Humidity | 10% to 90% (with no condensation) | ||||
| Atmosphere | Must be free from corrosive gas | ||||
| Terminal screw size | M3 | ||||
| Power interrupt time | AC power supply: 10 ms min. | ||||
| DC power supply: 2 ms min. | |||||
| CPU Unit weight | AC power | 650 g max. | 700 g max. | 800 g max. | 1,000 g max. |
| DC power | 550 g max. | 600 g max. | 700 g max. | 900 g max. | |
| Expansion Unit weight | Units with 20 I/O Points : 300 g max. | ||||
| Units with 8 Output Points : 250 g max. | |||||
| Units with 8 Input Points : 200 g max. | |||||
| MAD01 Analog I/O Unit : 150 g max. | |||||
| MAD11 Analog I/O Unit : 250 g max. | |||||
| AD041/DA041 Analog I/O units : 200 g max. | |||||
| Temperature Sensor Units : 250 g max. | |||||
| CompoBus/S I/O Link Units : 200 g max. | |||||
| DeviceNet I/O Link Unit : 200 g max. | |||||
| PROFIBUS-DP I/O Link Unit : 150 g max. | |||||