Overview
The OPTIWAVE 5400 is a 2-wire 24 GHz radar (FMCW) level transmitter for liquids in basic process applications. It is particularly designed for continuous, non-contact level measurement in the chemical, petrochemical, power as well as oil and gas industry. It can be equipped with a PP Drop antenna for condensing atmospheres and corrosive media but features also Metallic Horn antennas. Due to its high dynamic range, the 24 GHz radar can measure distances up to 100 m / 328 ft.
Product features and options depend on device configuration: Contact us to make sure that your preferred functionality can be combined in one device.
- 2-wire, loop-powered, with HART®7
-
PP Drop antenna:
- Insensitive to condensation
- Small beam angle (5° with DN150 / 6″ Drop antenna)
- Ellipsoidal shape and smooth surface to minimise scaling
- PP flange plate protection and cladded antenna extensions for corrosive media
- New DN100 / 4″ Drop antenna for distances up to 80 m / 262.5 ft
- 316L Metallic Horn antenna with optional purging system
-
TBM (Tank Bottom Management) ensures reliable measurement even in empty tanks:
- dedicated algorithms to filter and compensate for irregular radar wave reflections that occur at tank bottom when the vessel is empty
- allows for quick and easy commissioning of tanks regardless of their size, material or geometry
- ±2 mm / ±0.08″ accuracy
- Antenna extensions to suit any nozzle length
- Empty tank spectrum function eliminates false reflections caused by tank internals
- Large choice of flange and thread connections
- Large, backlit LCD screen with 4-button keypad for operation with bar magnet; no need to open the housing cover
- PACTware™, HART® DD and DTM provided free of charge with full functionality
- Extensive device diagnostics acc. to NAMUR NE 107
- SIL 2/3 certified for safety-related applications
- 3-year warranty
Specifications
Depending on selected device configuration
General information
Product type | Level transmitter |
Product family name | OPTIWAVE |
Product positioning | For liquids in basic process applications |
Measurement variables | Distance, Level, Mass, Reflection, Volume |
Measurement principle | Radar (FMCW) |
Level measurement type | Continuous measurement |
Contact to measured medium | No |
Interface measurement | No |
Redundancy | No |
Measured media | Liquids, Slurries, Pastes |
Measuring range (liquids) |
0…100 m/ 0…328 ft |
Ambient temperature |
-40…+80°C/ -40…+176°F |
Measuring point | Pressurised tank, Open tank, Stilling well, Open basin |
Operating conditions
Process pressure |
-1…16 barg/ -14.5…232 psig |
Process temperature |
-50…+130°C/ -58…+266°F |
Materials
Antenna | Polypropylene (PP) |
Gaskets | Ethylene propylene diene monomer (EPDM), Fluoroelastomer rubber (FKM/FPM), Kalrez® 6375 |
Process connections
Flange connections |
EN (1092-1): DN40…200 ASME (B 16.5): 1½…8'' JIS (B 2220): 40…200A |
Pressure ratings |
EN (1092-1): PN40 ASME (B 16.5): Cl 300# JIS (B 2220): 10k |
Thread connections |
Male: G1, G1½ 1 NPT, 1½ NPT |
Approvals/Standards
Certificates/Approvals Others | NACE, WHG, CRN / ASME B31.3 |
Certificates/Approvals Ex | ATEX, cQPSus, IECEx, NEPSI, EAC Ex, KCs |
Certificates/Approvals Safety | SIL 2/3 |
Ingress protection | IP66/68, NEMA4X/6P |
NAMUR compliance | NE 107, NE 21, NE 43, NE 53 |
Communication
Analogue outputs | 4…20 mA |
Digital outputs | FOUNDATION™ fieldbus, HART®, Profibus-PA |
Accuracy
Accuracy (liquids) |
±2 mm/ ±0.08 in |