Please login to use this feature. You can use this feature to add the product to your favourite list.
Close
You have added this product to your favorite list. Check My Favourite
Close
You have removed this product from your favourite list.
Close
Please login to use this feature. You can use this feature to add the company to your favourites list.
Close
This company has been added successfully. Check My Favourite
Close
This company has been removed from your favourite list.
Close
Please login to use this feature. You can use this feature to add the company to your inquiry cart.
Close
This company has been added to your inquiry cart.
Close
This company has been removed from your inquiry cart.
Close
This product has been added to your inquiry cart.
Close
This product has been removed from your inquiry cart.
Close
Maximum number of Product/Company has been reached in inquiry cart.
Close
EKG M & E SDN BHD
EKG M & E SDN BHD 201201033712 (1018200-D)
Waktu
Pejabat
Isnin - Jumaat 9:00 AM - 5:30 PM
Sabtu 9:00 AM - 1:00 PM
Ahad Closed
We′re closed on Public Holiday
Open Closed
SSM
PENGUNJUNG

24-Mar-2026

A ventilation control panel in a Kuala Lumpur or Selangor warehouse is the "brain" that coordinates your Exhaust Fans, Make-up Air Units (MAU), and HVLS fans. When this panel fails, the building’s Air Change Rate (ACH) drops, humidity spikes, and you may even face BOMBA compliance issues if the smoke spill interlock is compromised.

EKG M&E Sdn Bhd specializes in diagnosing and rectifying complex industrial control logic. Below is a professional troubleshooting guide for the most common M&E failures we encounter in the field.


1. The Variable Frequency Drive (VFD) Faults

Most modern warehouses use VSD/VFDs to save energy. If the fan isn't spinning, check the VFD screen for these common codes:

  • Over-Voltage (OV): Often caused by "Regenerative Braking" when a high-inertia fan (like an HVLS) is slowed down too quickly.

    • Fix: Adjust the "Deceleration Time" in the parameters.

  • Over-Current (OC): Indicates the motor is pulling more power than its nameplate rating. This usually means a mechanical blockage, a seized bearing, or a short-circuit in the motor windings.

  • Under-Voltage (UV): Common during Klang Valley thunderstorms. Power sags from the TNB grid trip the drive to protect the internal capacitors.

    • Fix: Perform a hard reset once the power stabilizes.

2. Fire Alarm (BOMBA) Interlock Issues

If the entire ventilation system has suddenly shut down and won't restart, the Fire Alarm Interlock is the primary suspect.

  • The Logic: Ventilation panels are wired to the Main Fire Alarm Panel (MFAP) via a "Dry Contact." If the fire alarm is triggered (or if there is a fault in the fire signal line), the ventilation system is programmed to shut down to prevent feeding oxygen to a fire.

  • Troubleshooting: Check if the "Fire Trip" indicator on your panel is illuminated. If there is no actual fire, the relay in the panel may be stuck or the signal cable from the MFAP may be severed.

3. Static Pressure & Sensor Failures

If your fans are running but at the wrong speed (too slow or constantly at 100%), the feedback loop is likely broken.

  • Pressure Transducers: These sensors measure the difference between indoor and outdoor pressure to maintain a Positive Pressure Shield. If the sensing tube is clogged with dust or insects, the VFD will "hunt" for a stable speed.

  • Phase Failure: If the panel's "Phase Healthy" light is off, one of the three incoming power phases from your Main Switchboard (MSB) is missing. Running a 3-phase motor on only 2 phases will lead to immediate motor burnout.


Common Control Panel Indicator Matrix

Symptom Probable Cause M&E Action Required
"Trip" Light On Thermal Overload / Motor Jam. Reset Overload & check motor Amps.
VFD Display Blank Blown Control Fuse / Power Loss. Check 24V DC / 230V AC control circuit.
Noisy Contactor Dust in Magnet / Low Coil Voltage. Clean contactor or replace coil.
Fans Run Backwards Incorrect Phase Rotation. Swap any two phases at the motor output.

Why Choose EKG M&E Sdn Bhd for Troubleshooting?

  • Root Cause Analysis: We don't just replace fuses. We use Power Quality Analyzers to determine if your panel failures are caused by harmonics, heat, or poor earthing.

  • Logic Optimization: We can reprogram your PLC or VFD to include "Soft-Starts" and "Load Shedding," reducing your peak demand charges on your TNB bill.

  • Strategic Support: Based in Kuala Lumpur, we provide emergency on-site repair and scheduled preventive maintenance for the region's largest logistics hubs.

Hantar mesej anda ke EKG M & E SDN BHD
Terima kasih untuk pertanyaan anda!
Perkhidmatan pelanggan kami akan menghubungi anda tidak lama lagi.
Nama Anda *
Nama Syarikat Anda
Emel Anda *
Nombor Telefon Anda *
Tajuk *
Mesej *
Captcha *
Pejabat Utama

EKG M & E SDN BHD 201201033712 (1018200-D)
27-2 & 27-3, Jalan Kuchai Maju, Kuchai Entrepreneur¡¯s Park, Off Jalan Kuchai Lama, 58200 Kuala Lumpur, Malaysia.

Tel:

Emel:
Laman Web: https://www.eakon.com.my
Laman Web: https://eakon.newpages.com.my/
Laman Web: https://eakon.onesync.my/

Melayari Melalui : Laman Utama - Klasifikasi - Syarikat - Tempat - Tag - Produk - Berita Baru dan Promosi - Jawatan Kosong - Laman Web Mudah Alih - Google - Keputusan SEO

NEWPAGES

Seni Jaya Logo
Brochure
Download
Our PackageContact Us