Common specifications for SB70G series
|
Item |
Description |
|
|
Input |
Rated voltage and frequency |
1 phase: 220v; 3-phase: 220v/380V/690V,50/60Hz |
|
Allowable range |
Voltage: 320~420V; voltage imbalance<3%; frequency:47~63 Hz |
|
|
output |
Output voltage |
3-phase, 0V~input voltage, with the error less than 5%. |
|
Output frequency range |
V/F control: 0.00~650.00Hz Vector control: 0.00~200.00Hz |
|
|
Basic specifications |
Motor control mode |
V/F control without PG, V/F control with PG, vector control without PG, vector control with PG, V/F separate control |
|
Steady-state speed precision |
Vector control without PG: ≤1% Vector control with PG: ≤0.02% |
|
|
Starting torque |
Not less than 150% of rated torque at 0.50Hz |
|
|
Overload capacity |
150% of rated current for 1 minute |
|
|
Frequency resolution |
Digital reference: 0.01Hz Analog reference: 0.1% of max. frequency |
|
|
Output frequency precision |
Analog reference: :±0.2% of max. frequency(25±10℃) Digital reference: 0.01Hz(-10~+40℃) |
|
|
Command source |
Keypad, terminal and communication. They can be switched over by terminals |
|
|
Frequency reference source |
Keypad, communication, UP/DOWN value, AI1, AI2, PFI and arithmetic unit |
|
|
Auxiliary frequency reference |
Achieves flexible frequency setting |
|
|
Torque boost |
Auto or manual torque boost |
|
|
V/F curve |
User defined V/F, linear V/F and 5 reduced-torque curves |
|
|
Accel/decel |
Linear or S-curve acceleration/deceleartion |
|
|
Jog |
Jog freuqnecy: 0.10~50.00Hz Jog accel/decel time: 0.1~60.0s |
|
|
Auto energy saving |
V/F curve is optimized automatically based on the load condition, achieving auto energy-saving run |
|
|
AVR |
Keeps the output voltage constant automatically when the voltage of power grid fluctuates |
|
|
Auto carrier regulation |
Carrier frequency is regulated automatically based on the load characteristic and ambient temperature |
|
|
Random PWM |
Regulates the tone of the motor noise |
|
|
Droop control |
Applicable to cases where multiple inverters drive the same load |
|
|
Momentary power failure |
Ensures uninterrupted operation by controlling the DC link voltage |
|
|
Dynamic braking |
Built-in braking unit and external braking resistor for models of 15kW or less |
|
|
DC braking |
Braking time: 0.0~60.0s Braking current: 0.0~100.0% of rated current |
|
|
PFI |
Highest input frequency: 50kHz |
|
|
PFO |
Open-collector pulse(square wave) output of 0~50kHz, programmable |
|
|
Analog input |
2 channels of analog input, voltage or current type, positive or negative |
|
|
Analog output |
2 channels of analog output, 0/4~20mA or 0/2~10V, programmable |
|
|
Digital input |
8 channels of optional multi-function digital input(leakage/source type) |
|
|
Digital output |
2 channels of optional multi-function digital output(leakage/source type); 2 channels of multi-function relay output |
|
|
Communication |
Bulti-in RS485 port, supporting Modbus protocol and USS commands |
|
|
Characteristic functions |
Process PID |
Two sets of PID parameters; multiple correction modes; free PID function |
|
Multiple PLC modes |
User can set 8 PLC run modes, with each having up to 48 stages. The mode can be selected by terminals. PLC status can be saved at power failure. |
|
|
Multi-speed select mode |
4 selection modes. Refer to F4-17 |
|
|
User defined menu |
30 user parameters can be defined |
|
|
Parameter display change |
Can display parameters different from the default ones |
|
|
Toreque control |
Torque/speed control can be switched by terminals. Multiple torque setting modes. |
|
|
Zero-servo |
Zero-speed position can be locked |
|
|
High-speed UP/DOWN counter |
Synchronous control, counting in production, stop contol by count and precise position control can be realized |
|
|
High-speed meter counter |
Stop control by length and length indication can be achieved |
|
|
Wobble |
Ensures even winding of textiles |
|
|
Programmable unit |
Comparator, logic unit, trigger, arithmetic unit, filter, multiple-way switch, timer |
|
|
kWh meter timer |
For adjustment of optimal energy saving strategy |
|
|
Protection functions |
Overcurrent, overvoltage, undervoltage, input/output phase loss, output short-circuit, overheating, motor overload, external fault, analog input disconnection, stall prevention, etc. |
|
|
Options |
Braking unit, remote control box, digital I/O expansion board, encoder interface board, analog input expansion board, keypad with copying function or potentiometer, keypad mounting box, keypad extension line,I/O reactor, EMI filter, Profibus-DP module, etc. |
|
|
Ambient |
Service site |
Altitude less than 1000 meters; indoor; no direct sunlight; free of dust,corrosive gases, inflammable gases, oil mist, water vapor, water drops, salt mist, etc. |
|
Temperature/humid |
-10~+40℃/20~90%RH, no condensation |
|
|
Storage temperature |
-20~+60℃ |
|
|
Vibration |
Less than 5.9m/s2(0.6g) |
|
|
Structure |
Protection degree |
IP20 |
|
Cooling method |
Forced air cooling, with fan control |
|