Rated power supply voltage |
100 to 240 VAC 50/60 Hz 100 to 125 VDC Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier) |
---|---|
Allowable voltage variable range | 85 to 110% of the power supply voltage |
Power consumption |
Relay ON: Approx. 2 VA (at 240 VAC 60 Hz)/Relay OFF: Approx. 1.3 VA (at 240 VAC 60 Hz) Relay ON: Approx. 1.6 W (at 240 VAC 60 Hz)/Relay OFF: Approx. 1.1 W (at 240 VAC 60 Hz) |
Reset voltage | 10% max. of rated supply voltage |
Number of time ranges | 18 |
Operation mode | Flicker OFF start |
Control output (Type) | Time-limit: DPDT |
Control output (Contact output) | Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value) |
Operating resetting | Time-limit operation/Time-limit reset or Self-reset |
Ambient temperature range |
Operating: -10 to 55 ¡æ (with no icing) Storage: -25 to 65 ¡æ (with no icing) |
Ambient humidity range | Operating: 35 to 85 % |
Accuracy of operating time |
±0.2% FS max. ±0.2% ±10 ms in a range of 1.2 s and 3 s |
Setting error | ±5% FS ±50 ms max. |
Reset time | 0.1 s max. |
Influence of voltage |
±0.2% FS max. ±0.2% ±10 ms in a range of 1.2 s and 3 s |
Influence of temperature | ±1% FS max. (±1% ±10 ms in a range of 1.2 s and 3 s) |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength |
Between current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min |
Impulse withstand voltage |
Between power terminals: 5 kV Between current carrying terminals and exposed non-current carrying metal parts: 5 kV |
Noise immunity | ±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) |
Static immunity | Mulfunction: 8 kV, Destruction: 15 kV |
Vibration resistance |
Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
Shock resistance |
Destruction: 980 m/s2, 3 times each in 6 directions Malfunction: 98 m/s2, 3 times each in 6 directions |
Life expectancy (relay output) |
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h) Mechanical: 20 million operations min. (under no load at 1,800 operations/h) |
Degree of protection | IP40 (panel surface) |
Connecting method | 8-pin round socket |
Weight | Approx. 100 g |
Applicable socket | P2CF-08/ P2CF-08-E/ PF085A/ P3G-08/ PL08/ PL08-Q/ PLE08-0 |