Technical data | EL2024 |
---|---|
Connection technology | 2-wire |
Number of outputs | 4 |
Nominal voltage | 24 V DC (-15%/+20%) |
Load type | ohmic, inductive, lamp load |
Distributed clocks | – |
Max. output current | 2.0 A (short-circuit proof) per channel |
Short-circuit current | typ. < 70 A |
Reverse voltage protection | yes |
Breaking energy | < 1.7 J/channel |
Switching times | typ. TON: 40 µs, typ. TOFF: 200 µs |
Current consumption E-bus | typ. 120 mA |
Current consumption power contacts | typ. 13 mA + load |
Bit width in the process image | 4 outputs |
Configuration | no address or configuration setting |
Electrical isolation | 500 V (E-bus/field potential) |
Weight | approx. 55 g |
Operating temperature | -25…+60°C |
Storage temperature | -40…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE, CCC, UL, ATEX, IECEx |
Ex marking |
ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |