4-digit programmable projection
-
multifunction input UNI (DC, PM, RTD, T/C, DU)
-
digital filters, tare, linearization, excitation
-
size of DIN 96 x 48 mm
-
power supply 10…30 V AC/DC or 80…250 V AC/DC
Options
-
comparators
-
data output
-
analog output
-
measured data record
-
three-color display - 20 mm
Technical data:
InputDCRangemenu selectable
±60 mV> 100 MOhmInput U±150 mV> 100 MOhmInput U±300 mV> 100 MOhmInput U±1200 mV> 100 MOhmInput UPMRangemenu selectable
0…20 mA< 400 mVInput I4…20 mA< 400 mVInput I±2 V1 MOhmInput U±5 V1 MOhmInput U±10 V1 MOhmInput U±40 V1 MOhmInput UOHMRange0…100 Ohm
0…1 kOhm
0…10 kOhm
0…100 kOhmConnection2, 3 or 4-wireRTDTypeEU > 100/500/1 000 Ohm s 3 850 ppm/°C-50°…450°CRU > 50 Ohm s 3 910 ppm/°C-200°…1 100°CRU > 100 Ohm s 3 910 ppm/°C-200°…450°CUS > 100 Ohm s 3 920 ppm/°C-50°…450°CConnection2, 3 or 4-wireNiTypeNi 1 000/10 000 s 5 000 ppm/°C-50°…250°CNi 1 000/10 000 s 6 180 ppm/°C-50°…250°CConnection2, 3 or 4-wireCuTypeCu 50/100 with 4 260 ppm/°C-50°…200°CCu 50/100 with 4 280 ppm/°C-200°…200°CConnection2-, 3-, or 4-wireT/CTypeJ (Fe-CuNi)-200°…900°CK (NiCr-Ni)-200°…1 300°CT (Cu-CuNi)-200°…400°CE (NiCr-CuNi)-200°…690°CB (PtRh30-PtRh6)300°…1 820°CS (PtRh10-Pt)-50°…1 760°CR (Pt13Rh-Pt)-50°…1 740°CN (Omegalloy)-200°…1 300°CL (Fe-CuNi)-200°…900°CDUPotentiometer power supply2 VDC/6 mA, potentiometer resistance > 500 OhmExpansion ''A'' (DC ranges)Rangemenu selectable
±0,1 A<300 mVInput I±0,25 A<300 mVInput I±0,5 A<300 mVInput I±1 A<30 mVInput I±5 A<160 mVInput I±100 V20 MOhmInput U±250 V20 MOhmInput U±500 V20 MOhmInput UExpansion ''B'' 3x PMRangemenu selectable
0…20 mA<400 mVInput 2, 3, 4 - I4…20 mA<400 mVInput 2, 3, 4 - I±2 V1 MOhmInput 2, 3, 4 - U±5 V1 MOhmInput 2, 3, 4 - U±10 V1 MOhmInput 2, 3, 4 - U±40 V1 MOhmInput 2, 3, 4 - UExternal inputsNumber3 inputs, on contactFunctionsOFF No function HOLD Stopping measurement (option: Display - Analog output - Limits) BLOK.K. Blocking front panel keys B.HESL. Blocking access to the LIGHT/PROFI menu TARA Tare activation NUL. TA. Resetting tare NUL. M.M. Resetting Min/Max. value ULOZ Data record activation (extention of RTC/FAST) NUL. PA. Resetting memory (extention of RTC/FAST) KAN. A Value display ''Channel A'' FIL. A Value display ''Channel A'' after processing by a digital filter MAT. FN. Value display ''Mathematical function'' PREP. Switching channels (extention ''B'') ProjectionDisplay range-99999…999999, single-coloured 14-segment LED
-999…9999, 3-coloured 7-segment LEDDisplay height14 mm, 20 mmDisplay colourred, green, red/green/orangeSignalizing LED1, 2, 3, 4 Limits L1, L2, L3, L4 (red) T Tare (green) M Min./Max. value (green) A, B, C, D Channels A, B, C, D (orange) Descriptionthe last two digits of the display can be used to display measured variables (only 14 mm display)Decimal pointmenu adjustable - fixed or floatingDisplay brightnessmenu adjustableDisplayed valuesKan A Value from channel A Fil. A Value from channel A after digital filter adjustment Mat. Fn. Value of mathematical function Max. Maximum value Min. Minimum value SettingsControlThe device is controlled and set by five buttons on the front panel
Selected functions can also be controlled via external inputsMenuLIGHT contains only items necessary for basic device settings with password access PROFI Full device settings with password access USER User menu of any item, selected from LIGHT/PROFI. Access without password. Optional functionsButtons ''Left'', ''Up'', ''Down'', ''Enter'' can be assigned additional optional features
ZAKAZ button has no function NUL. M.M. Resetting Min/Max vaslues NUL. TA. Tare reset MENU Direct access to the selected menu item DOC. H. Temporary projection of selected values TARA Activating function Tare ULOZ Starting recording of the measured data into device memory NUL. PA. Resetting memory of the measured data OM LinkCompany communication interface for operation, setting and update of device firmware
OM Link program is also designed for visualization and filing of meas. values from more instrumentsInstrument accuracy and functionalityTemperature coefficient50 ppm/°CAccuracy±0,1 % of range + 1 digit
±0,15 % of range + 1 digit (RTD, T/C)
(for projection 9999 and 5 measur./s)Accuracy of cold junction measurement±1,5°CRate0,1…40 measur./sOverload capacity2x; 10x (t < 30 ms) - not for > 200 V and 5 AResolution (RTD, T/C)1°C, 0,1°C, 0,01°CWire compensation (RTD, OHM)< 30 OhmCold junction compensationadjustable -20°…99°C, automaticLinearizationlinear interpolation in 50 points (only via OM Link)Digital filtersarithmetic mean from 2…100 measurements floating mean from 2…30 measurements exponential mean from 2…100 measurements rounding setting projection step for display FunctionsTare designed to reset display on non-zero input signal Fixed tare preset fixed tare Min/max value registration of min./max. value achieved during measurement Peak value display shows only max. or min. values Math. functionspolynom, 1/x, logarithm, exponential, power, rootMath. operations between inputssum and quotientData recordMeasured data recording into the memory
RTC period - 1 s…1 day, time-date-display value, < 266k data, 15 ppm/°C FAST 40 records/s, display value, < 8k data Watch-dogreset after 400 msCalibrationat 25°C and 40 % r.h.ComparatorsTypeDigital, menu adjustable, contact connect. < 30 msModeHysteresis switch. point, hysteresis band ''Mez ± 1/2 Hys.'' and time (0 ... 99.9 s) determ. switching delay From-To output interval ON and OFF Dose period, its multiples and time (0 ... 99.9 s), during which the output is active Output1x relay, switch-over contact (250 VAC/30 VDC, 3 A)
2x relay, switch-over contact (250 VAC/30 VDC, 3 A)
1x relay, switch on contact (250 VAC/30 VDC, 3A)
2x relay, switch on contact (250 VAC/30 VDC, 3 A)
2x bistable relay (250 VAC/30 VDC, 3A)
3x relay, 2x switch on + 1x switch-over contact (250 VAC/30 VDC, 3A)
4x relay, 2x switch on + 2x switch-over contact (250 VAC/30 VDC, 3A)
2x open collector (30 VDC/100 mA)
4x open collector (30 VDC/100 mA)
2x open collector (30 VDC/100 mA) + 2x relay, CO contact (250 VAC/30 VDC, 3 A)
2x SSR (250 VAC/1 A)Data outputsProtocolASCII, MESSBUS, MODBUS - RTU, PROFIBUS DPData format8 bits + no parity + 1 stop bit (ASCII)
7 bits + even parity + 1 stop bit (Messbus)Rate600…230 400 Baud
0,0096…12 MBaud (PROFIBUS)RS 232isolatedRS 485isolated, addressing max. 31 instrumentsAnalogue outputsTypeIsolated, programmable with a 16-bit D / A converter, type and range are menu selectableTemperature coefficient15 ppm/°CNonlinearity±0,1 % of rangeRateresponse to value change < 1 msRanges0...2 V, 0...5 V, 0...10 V, ±10 V, 0...5 mA, 0...20 mA, 4...20 mACompensation600 Ohm/12 V, 1 000 Ohm/24 VError stateat range of 4...20mA
error message indication (<3.0 mA)
Detection of current loop interruptionSensor excitationAdjustable5…24 VDC/max. 1,2 WPower supplyPower supply10…30 V AC/DC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolated
80…250 V AC/DC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolatedCurrent draw< 9,4 W/9,2 VAPower supply protectionPower supply is protected by a fuse inside the instrumentOperating conditionsConnectionconnector terminal board, cable section < 1,5/2,5 mm2Operating temperature-20°…60°CStorage temperature-20°…80°CProtection classIP64 (front panel only)El. safetyEN 61010-1, A2Dielectric strength4 kVAC within 1 min. between pow. supply and input
4 kVAC within 1 min. between pow. supply and data/anal. output
4 kVAC within 1 min. between input and relay output
2,5 kVAC within 1 min.between input and data/anal. outputInsulation resistancefor polution degree II, measuring cat. III.
power supply 670 V (ZI), 300 V (Di)* input, output, PN 300 V (ZI), 150 V (Di)* EMCEN 61326-1Seismic capacityIEC 980: 1993, par.6SW validationCompliance with IEC 62138, 61226, class B, CMechanical propertiesMaterialNoryl GFN2 SE1, non-inflammable UL 94 V-IDimensions96 x 48 x 120 mm (w x h x d)Panel cutout90,5 x 45 mm (w x h)