Description
- Solid conductor of thermocouple material to table page 48
- Insulation polyvinylchloride YI3 or polyethylene 2Yl1 to DIN VDE 0207
- Cores twisted to form a pair
- Colour code: see table page 55
- Wrapping of polyester tapes
- Collective screen of plastic bonded aluminium tape with tinned drain wire 7 x 0.3mm, approx. 25% overlap
- Outer sheath of polyvinyloride YM1 to DIN VDE 0207, colour: see page 55, for intrinsically safe systems: blue with identification stripe
Cable Identification:
KERPEN special EXTENSION CABLE 300V or
KERPEN special COMPENSATING CABLE 300V
Abbreviations:
RT- thermocoupe extension and compensating cable
2Y insulation of polyethylene
Y insulation of polyvinylchloride
Yv thicker sheath of polyvinylchloride
(St) collective screen
Application:
for transmission of thermoelectic voltage from measuring junction to reference junction
Use:
for indoor and outdoor installation and direct burial
Temperature rating:
during operation: -30°C up to +70°C
during installation: -5°C up to +50°C
Min bending radius:
7,5 x d (d=overall diameter)
Other properties:
flame retardant to DIN VDE 0472 part 804