Key Features
- Intrinsically Safe with European, USA, South African, and Indian approvals
- Approved SIL 2 and SIL 3
- For use with PLC/DCS systems
- Temperature output
- Compression Crystal Construction
Industries
Building services, Pulp and Paper, Mining, Metals, Utilities, Automotive, Water, Pharmaceutical
Applications
Fans, Motors, Pumps, Compressors, Centrifuges, Conveyors, Air Handlers, Gearboxes, Rolls, Dryers, Presses, Cooling, VAC, Spindles, Machine Tooling, Process Equipment
| Sensitivity |
±10%, Nominal 80Hz at 22°C / 72°F |
|---|---|
| Operating Temperature Range |
Ex ia IIC T4 Ga (-40°C ≤ Ta ≤ +110°C) (Gas), Ex ia IIC T6 Ga (-40°C ≤ Ta ≤ +60°C) (Gas), Ex ia IIIC T130°C IP65 Da ( -40°C ≤ Ta ≤ +110°C) (Dust), Ex ia IIIC T80°C IP65 Da ( -40°C ≤ Ta ≤ +60°C) (Dust) |
| Sealing |
IP67 |
| EMC |
EN61326-1:2013 |
| Case Material |
Stainless Steel |
| Sensing Element/Construction |
PZT/Compression |
| Weight |
150gms/ 5.2 oz (nominal) |
| Screened Cable Assembly |
HS-AC010 – straight, HS-AC011 – right angle |
| Top/Side Entry |
Top Entry |
| Feature |
Intrinsically Safe |
| Connector/Cable Type |
M12 Connector |
| Output |
4-20mA Acceleration |
| Axis |
Single (Standard) |




VN 19745
US 6930
AR 4247
BR 2812
CN 2418
EC 1617
SG 1138
MX 901