| Supply voltage | ||
| Load voltage L+ | ||
| ● Rated value (DC) | 120 V | |
| Load voltage L1 | ||
| ● Rated value (AC) | 230 V | |
| Input current | ||
| from supply voltage L+, max. | 125 mA | |
| from backplane bus 5 V DC, max. | 40 mA | |
| Power loss | ||
| Power loss, typ. | 3.2 W | |
| Digital outputs | ||
| Number of digital outputs | 8; Relays | |
| Short-circuit protection | No; to be provided externally | |
| Controlling a digital input | Yes | |
| Switching capacity of the outputs | ||
| ● on lamp load, max. | 1 500 W; 230 V AC | |
| ● Low energy/fluorescent lamps with electronic control gear | 10x 58 W | |
| ● Fluorescent tubes, conventionally compensated | 1x 58 W | |
| ● Fluorescent tubes, uncompensated | 10x 58 W | |
| Output current | ||
| ● for signal "1" rated value | 5 A | |
| ● for signal "1" minimum load current | 5 mA | |
| Parallel switching of two outputs | ||
| ● for uprating | No | |
| ● for redundant control of a load | Yes | |
| Switching frequency | ||
| ● with resistive load, max. | 2 Hz | |
| ● with inductive load, max. | 0.5 Hz | |
| ● With inductive load (to IEC 60947-5-1, DC13/AC15), max. | 0.5 Hz | |
| ● on lamp load, max. | 2 Hz | |
| ● mechanical, max. | 10 Hz | |
| Total current of the outputs (per group) | ||
| horizontal installation | ||
| — up to 60 °C, max. | 5 A | |
| vertical installation | ||
| — up to 40 °C, max. | 5 A | |
| Relay outputs | ||
| ● Rated supply voltage of relay coil L+ (DC) | 24 V | |
| ● Contact connection (internal) | No | |
| ● Number of operating cycles, max. | 300 000; 300 000 (24 V DC, at 2 A); 200 000 (120 V AC, at 3 A); 100 000 (230 V AC, at 3 A) | |
| Switching capacity of contacts | ||
| — with inductive load, max. | 3 A; 3 A (230 V DC), 2 A (24 V AC) | |
| — with resistive load, max. | 8 A; 8 A (230 V DC), 5 A (24 V AC) | |
| — Thermal continuous current, max. | 8 A | |
| Cable length | ||
| ● shielded, max. | 1 000 m | |
| ● unshielded, max. | 600 m | |
| Interrupts/diagnostics/status information | ||
| Alarms | No | |
| Diagnostics function | No | |
| Alarms | ||
| ● Diagnostic alarm | No | |
| Diagnoses | ||
| ● Wire-break | No | |
| ● Short-circuit | No | |
| ● Fuse blown | No | |
| ● missing load voltage | No | |
| Diagnostics indication LED | ||
| ● Rated load voltage PWR (green) | No | |
| ● Fuse OK FSG (green) | No | |
| ● Status indicator digital output (green) | Yes | |
| Potential separation | ||
| Potential separation digital outputs | ||
| ● between the channels | Yes | |
| ● between the channels, in groups of | 1 | |
| ● between the channels and backplane bus | Yes; Optocoupler | |
| Isolation | ||
| Isolation tested with | 2 000 V AC | |
| connection method | ||
| required front connector | 40-pin | |
| Dimensions | ||
| Width | 40 mm | |
| Height | 125 mm | |
| Depth | 120 mm | |
| Weights | ||
| Weight, approx. | 320 g | |





BR 23757
US 7685
VN 5949
MY 2743
IN 2230
AR 2128
GB 1692
MX 1655