Key Features
- Intrinsically Safe with European, USA, South African, and Indian approvals
- Approved SIL 2 and SIL 3
- For use with PLC/DCS systems
- Temperature output
- Compression Crystal Construction
Industries
Building services, Pulp and Paper, Mining, Metals, Utilities, Automotive, Water, Pharmaceutical
Applications
Fans, Motors, Pumps, Compressors, Centrifuges, Conveyors, Air Handlers, Gearboxes, Rolls, Dryers, Presses, Cooling, VAC, Spindles, Machine Tooling, Process Equipment
| Sensitivity |
±10%, Nominal 80Hz at 22°C / 72°F |
|---|---|
| Operating Temperature Range |
Ex ia IIC T4 Ga (-40°C ≤ Ta ≤ +110°C) (Gas), Ex ia IIC T6 Ga (-40°C ≤ Ta ≤ +60°C) (Gas), Ex ia IIIC T130°C IP65 Da ( -40°C ≤ Ta ≤ +110°C) (Dust), Ex ia IIIC T80°C IP65 Da ( -40°C ≤ Ta ≤ +60°C) (Dust) |
| Sealing |
IP67 |
| EMC |
EN61326-1:2013 |
| Case Material |
Stainless Steel |
| Sensing Element/Construction |
PZT/Compression |
| Weight |
150gms/ 5.2 oz (nominal) |
| Screened Cable Assembly |
HS-AC010 – straight, HS-AC011 – right angle |
| Top/Side Entry |
Top Entry |
| Feature |
Intrinsically Safe |
| Connector/Cable Type |
M12 Connector |
| Output |
4-20mA Acceleration |
| Axis |
Single (Standard) |




BR 9045
VN 6547
US 2976
CN 1528
AR 1503
MY 1201
SG 653
IN 598