Type ID Number |
MS22-RI/85-265VUC M0508010 |
|
Power Supply Supply voltage Power consumption |
85-265 VAC/DC 4.5 VA |
|
Function Speed range Switching point adjustment range |
overspeed/underspeed 0.6-100,000 pulses/min 10-100% |
| Input frequency | |
| Minimum pulse duration | ?:0.2 ms |
|
Minimum pause duration Hysteresis Start-up time delay |
?:0.2 ms approx. 10% 0.5-30 s (adjust., ten positions) |
| Temperature drift - frequency | 0.005%/K of full scale |
| Temperature drift - analog output | 0.005%/K of full scale |
| Linearity error | 0.1% of full scale |
|
Input Circuits NAMUR input - Nominal operating characteristics |
NAMUR, 3-wire PNP per DIN 19 234 (term. 9/10) V = 8.2 V, I = 8.2 mA |
| - Switching threshold | 1.4 mA I 1.8 mA |
| - Wire-break threshold | 0.15 mA |
|
- Short-circuit threshold 3-wire input |
?:6 mA PNP (term. 9/10/11) |
|
V 15 V, I 30 mA 0-5 VDC 10-30 VDC |
| Output Circuits | 1 SPDT relay, 1 analog output |
| - Contact material | AgCdO + 3 µ Au |
| - Switching voltage | 250 V |
| - Switching current | 2 A |
|
- Switching capacity Analog output |
500 VA/60 W |
| - Current source | 0/4-20 mA (load impedance 600 ν) |
| LED Indications | |
|
-Power “ON” and valid input
-Output energized
-Input pulse
-Fault indication
|
green yellow yellow red |